Pump Head Pressure Calculator

Enter the static lift, pipe run and required pressure to find the total head your pump must deliver.

How it is calculated

The tool adds three heads, all in metres of water column.

friction head = pipe_length × friction_loss ÷ 100
pressure head = pressure_bar × 10.1972
total head = static_lift + friction head + pressure head
total in bar = total head ÷ 10.1972

Static Lift is the vertical rise in m, Pipe Length the pipe run in m, Friction Loss is the head lost per 100 m of pipe (m/100 m), and Required Outlet Pressure is the pressure wanted at the outlet. You must supply the friction figure yourself from the pipe size, flow rate and material; the tool does not work it out. Inputs cannot be negative, all four fields are required, and a friction loss above 100 m per 100 m of pipe, or a total of zero, gives no result. Results are rounded to two decimals. Fittings and valves are not added separately.

Worked example

Water must rise 15 m through 120 m of pipe that loses 4 m per 100 m, with 2.5 bar wanted at the outlet. Friction head: 120 × 4 ÷ 100 = 4.80 m. Pressure head: 2.5 × 10.1972 = 25.49 m. Total: 15 + 4.80 + 25.49 = 45.29 m, which is 4.44 bar. Choose a pump that delivers your flow at about that head.

Try this example →

Common mistakes

  • Entering the total friction loss of the pipe in the friction field. It is the loss per 100 m; the tool multiplies by the length itself.
  • Leaving the outlet pressure at zero for a sprinkler or nozzle that needs, say, 2 bar. The pressure head is then missing from the total.
  • Typing the pressure in psi or kPa. The field is bar, so 30 psi is about 2.1 bar.
  • Entering the horizontal distance as static lift. Only the vertical rise counts there; the horizontal run goes in pipe length.
  • Ignoring that the friction figure depends on the flow rate. A value looked up for a low flow will understate the head if the pump delivers more.

About this calculator

Total pump head is the sum of three components a pump must overcome: static lift (the vertical height the water must be raised), friction loss (energy lost to resistance along the pipe run, which grows with pipe length and flow rate and shrinks with larger pipe diameter), and the pressure head needed at the outlet, converted from pressure units to an equivalent height in meters — roughly 10.2 meters of head per bar of required pressure.

Irrigation installers, plumbers and pool technicians calculate total head before selecting a pump, because a pump's rated flow rate is only accurate at a specific head — undersizing the pump for the actual head means weak flow or pressure at the outlet, while oversizing wastes energy and money on a pump doing more work than the system needs.